Wednesday, January 28, 2015

Useful App for Field Quality Control Testing of Installed Windows, Storefront, Curtain Wall & Skylights

Construction Friendly App:


If you have a project that requires testing of installed windows, Storefront, Curtain Wall or Skylights using the ASTM E-1105 Test Procedure, take a few minutes to add this app to your smart phone.

Its simple to use and can provide the proper get pressure for you with ease.
 


GE Launches New Pressure Converter Application for iPhone

New application allows field personnel to perform 28 types of calculations
Billerica, MA - June 9, 2010 - GE Sensing brings pressure unit conversion mobile with the new Pressure Converter, a mobile application for measuring units of pressure in an industrial setting. Available in the Apple Application Store for free, this mobile tool can easily perform 28 different types of pressure calculations. The Pressure Converter is ideal for plant, process and service engineers, site contractors and laboratory technicians in oil & gas, power generation and other industrial settings, where basic conversion may be needed but a computer is not always easily accessible.
"The Pressure Converter application lets our customers quickly and easily access our pressure unit conversion tool when they are in the field," said Graham Dawber, Leader of the pressure product line at GE Sensing. "This is the first in a number of free applications we are developing to help our customers access useful information through their mobile device."

Visit the Apple Application Store to download




Tuesday, June 10, 2014

Building Envelope Review - Failure Analysis - Leak Locating - Field Testing - Roof Uplift

Recon has been busy.  From several projects around the Tampa, FL area to Orlando, Gainesville, Jacksonville and Pensacola; we even managed to squeeze in a project up in Virginia over the past few weeks.

Field testing with the ASTM E 1105 / AAMA 502 & 503 has been getting a lot of attention on the ever busy apartment building boom thats ongoing.

Working directly for the owner on a large apartment development is keeping envelope details on track and quality high.  After determining the best configuration of flashing and wrap on a mock-up, its been an ongoing effort to ensure the buildings follow.

Plenty of FM - 152 roof uplift  requests are coming in, it looks like the fall will be busy in that regard.

Don't forget Electronic Vector Mapping is available for live roof installs to ensure no breaches or pinholes exist in the membrane before installing media and live plantings.  Contact us today to get surprised by how affordable we've made it. 407-948-4983.

When the next tropical event happens, we expect to be busy providing cause and origin on leak issues on large custom coastal homes


building envelope consultants

We've had a few preparing for storm season by ensuring their windows and envelope are tight and ready for the impending wind driven rain of the wet season.

407-948-4983

Wednesday, April 30, 2014

Patriot Ridge - Radius Curtain Wall Field Testing by Recon Independent Assessments

Past Project:






Recon Independent Assessments provided water penetration resistance field testing on the installed curtain wall during construction of Patriot Ridge.  As a Qualified Third Party Testing Agency, Recon is available to provide field testing of windows, storefront, curtain wall & skylight systems on your project.



We're looking for more projects, contact us today for a proposal.  From building envelope design review, field quality control, building envelope consulting & field testing; Recon is available nationwide.


407-948-4983
Recon Independent Assessments

RTS Bus Maintenance Facility Water Penetration Resistance Field Testing ASTM E-1105

Recon Independent Assessments
Field Report


Recon Independent Assessments is providing field testing on the RTS Bus Maintenance Facility as well as several other projects around Gainesville, FL.

Let us know if you need building envelope design review or field quality control consulting services on your project.  We're looking for more projects with owners who believe in building the best building available.

407-948-4983 

Monday, August 26, 2013

Design Review - Building Envelope Review - Consulting

Recon Independent Assessments provides valuable insight on projects in the design phase as well as during construction to help avoid potentially problematic details that would allow for water infiltration through the building envelope.

Boston, MA Area High School Addition


Recent building envelope design review projects include hospital renovations in Baltimore, a Federal Courthouse remediation in South Florida, a Federal Courthouse Addition in Louisville, Kentucky, a tunnel form Multi-Family Apartment Building in North Florida, a Municipal Complex in Raleigh, North Carolina, a Federal Building in Hampton, Virginia and a multi-story Office Building in Central Florida.

MOB Baltimore, MD


Let our experience guide you on your next project.  We bring years of experience in providing failure analysis to the table to help head off problems with the building envelope.

Our services are a firewall to future design issues that could lead to leaks and damage to your reputation.

Contact us today to discuss your project and get us involved.

We look forward to helping make your project a success.

866-584-6868


Project Offices Nationwide




Saturday, October 6, 2012

Busy Fall Schedule

New high school field quality control testing

New high school field quality control testing

New high school field quality control testing

New high school field quality control testing
Recon Independent Assessments has been steady at it providing services ranging from field quality control testing of newly installed windows, storefront and curtain wall to conducting leak investigations and providing plan review, submittals and envelope consulting.

We are available nationwide and welcome the opportunity to join your project.

Contacting us is easy:  866-584-6868

Site Review on Hospital Renovation

Site Review on Hospital Renovation

Site Review on Hospital Renovation

Site Review on Hospital Renovation

Site Review on Hospital Renovation

Site Review on Hospital Renovation

Multi-family field quality control testing

Multi-family field quality control testing

Multi-family field quality control testing

Multi-family field quality control testing

If your project is ready for positive, outgoing and knowledgable field testing or envelope consulting, look no further than Recon Independent Assessments.

The consultants you'll see on site are the owners of the company.

Every project is executed in a manner that leads us to our next one.

Monday, June 18, 2012

Affordable & Reliable Field Quality Control Testing for Water Penetration Resistance - ASTM E 1105

Recon Independent Assessments - 866-584-6868 - continues to provide testing and evaluation of newly installed windows, curtain wall, storefront and skylights as a Qualified Third Party Testing Agency.

Recent Field Testing in Orlando Florida provided valuable information to the Project Team charged with delivering a watertight building envelope on a high school replacement project.

The ASTM E 1105 was used to field test for water penetration resistance of installed curtain wall sections.

ASTM E1105 Building Envelope Testing ASTM E783

ASTM E 1105 Water Test Recon Independent Assessments

Recon Independent Assessments ASTM E1105

ASTM E 1105 Spray Rack Qualified Independent Testing Agency

Manometer Recon Independent Assessments ASTM E1105

Recon Independent Assessments ASTM E1105 Testing Window



Building Envelope Recon Independent Assessments ASTM




ASTM E 1105 Recon Independent Assessments Building Envelope


Contact Recon Independent Assessments to receive a proposal for testing based on your project specifications.

866-584-6868

Tuesday, June 12, 2012

Building Envelope Testing Courtesy of Mother Nature

Recent storms throughout the Southeast United States have brought with them excessive 24 hour rainfall totals and high winds.

From rooftops and skylights to windows and curtain walls, the water penetration resistance of many structures has been tested in real world conditions that far exceed the test protocols that are typically seen in field quality control testing.

The ASTM E 1105 typically uses a test pressure equivalent to 1/3 the water test pressure used in the laboratory test, ASTM E 331.

After rain events like the ones that have been felt recently, many facilities managers will be looking for the source of unwanted water inside the building envelope.

Recon Independent Assessments has been providing building envelope consulting services to quite a few clients to locate the source of leaks so that the repairs are made accurately.

It is very often diagnosed by owners initially as; "the curtain wall leaked".

In many cases it isn't.

Recon provides a fresh and unbiased set of eyes to evaluate the structure with one goal in mind, finding the responsible component that allowed for water to penetrate the building envelope.

As a Qualified Third Party Testing Agency, we see a lot of conditions during construction that gives us insight into where potential problems may exist.

As providers of Expert Opinions in Construction Litigation we also understand the importance of addressing owners' concerns professionally and accurately.  By being proactive and involving a third party to conduct a post event investigation, many times owners never consider litigation.

Failure to address leaks professionally and successfully can lead to court proceedings.

Recon Independent Assessments is available at considerably less expense in the role of third party moisture intrusion investigation consultant versus as opposing counsel's expert.

Our goal is to pursue the truth.  By seeking it, time and money is always saved.

To learn more about our capabilities and to receive a quote for your specific problem or testing needs, call us anytime:  

866-584-6868

Tuesday, May 15, 2012

Division 8 Specifications - Laboratory Testing vs. Field Testing

A few months ago, Recon Independent Assessments provided field quality control testing on a project that was installing both curtain wall and storefront systems.

During the first round of testing, quite a few failures were observed using the ASTM E 1105, the field testing specification called for in the project specifications.

After the installer evaluated the cause of the failures, they conducted remedial work to ensure the installation was watertight.  Re-testing was called for and Recon returned to test the installed systems once again.

Unfortunately, water penetration continued in both systems.

Nearly six months passed without word from the project regarding additional re-testing being scheduled to confirm a second round of remedial work had solved the leaking.

The installer contacted Recon asking questions regarding the test pressures that had been used during the previous field testing.

The project specifications called for a curtain wall that had evidenced water penetration resistance at 12 PSF during laboratory testing using an ASTM E 331.  The project specifications called for the use of the ASTM E 1105 to evaluate the installation in the field.  A knowledgeable professional would know that the ASTM E 1105 requires a test pressure in the field of 2/3 of the pressure used in the laboratory (8 PSF).

Despite documentation detailing the use of the ASTM E 1105 and references to the project specifications that determined the test pressures, the installer was questioning the testing rather than focusing on providing a solution to the failures.

Care in selecting a glazing contractor that understands a project's specifications and has the ability to demonstrate quality work can best prepare your project for success.  Ask for proof of past testing success from the contractor that is bidding, price should not be the only determining factor in awarding a bid.

If you ignore testing or engage contractors that do not understand its importance and you may be seeing this:

In an effort to resolve leaks, an unknown "sealant" was applied within the storefront system.

Despite the addition of the "sealant", leaks continue to plague the project.

Recon Independent Assessments is available to provide continuing education for your staff.  Knowledge is power.  Contact us today to learn how our lunch and learn presentations can lead to higher quality results on your project.

866-584-6868 



Wednesday, April 4, 2012

Orange Park Medical Center Vertical Expansion Field Testing

Recon Independent Assessments is providing field testing of installed hurricane impact resistant windows and curtain wall on the vertical expansion project at Orange Park Medical Center.

As a Qualified Third Party Testing Agency, Recon inspects and tests newly installed fenestration and glazing to ensure that water penetration resistance is achieved.  The critical joints between the glazing and fenestration to the surrounding construction is key to ensuring a watertight building envelope.  Using test methods contained within ASTM E 1105 provides a measure of confidence to the contractor and owner that the installers have used best practices and have successfully completed their scope of work.

ASTM E 1105

Vertical Expansion

866-584-6868

ASTM E-1105

Recon 866-584-6868

Tuesday, March 27, 2012

University of North Florida - Jacksonville Curtain Wall Field Testing

The field quality control testing called for in the project documents includes testing at 10 - 30 & 70% of completion of Division 8 work, including aluminum windows and curtain walls.

Recon arrived on site this morning to continue testing to help ensure the project's successful completion.

Call Recon Independent Assessments
866-584-6868
Field Quality Control Testing
&
Building Envelope Consulting

Thursday, March 22, 2012

Recon Independent Assessments

The past two and a half months have been a blur.  Projects requiring windows, curtain walls and roofing  materials field testing has taken us across the state of Florida.

Testing in Jacksonville on construction projects that included a new university facility, a condominium retrofit and upgrade and a new hospital tower required both ASTM E 1105 & AAMA 501.2 test procedures.

Orlando projects used AAMA 502 & 503 test standards to evaluate newly installed windows and storefront entrances at several schools and a retirement community tower project.

A medical research facility in south Florida and hospital on the east coast required testing using FM-152 roof uplift testing.

We are humbled by the trust that we've received from our clients and will continue to build on that trust each and every time we support their mission.

Operable Window Field Testing of School Project

Moisture Intrusion Investigation on Coastal Condominium

ASTM E 1105 Field Testing 

University Facilities Field Testing 

Identifying Problems Early In A Project Prevents Future Problems

Wednesday, October 12, 2011

Baltimore Healthcare Project


Orlando School Project

Norfolk Military Project

Jacksonville University Project

Hawaii Community College Project

Washington DC Commercial Office Project

ASTM E 1105 Field Quality Control

AAMA 502 Field Quality Control


The Industry Leader For Independent Third Party Testing

• ASTM E 1105 Field Test for Water Penetration / Static Pressure.
• ASTM E 783 Field Test for Air Infiltration.
• AAMA 501.2 Field Check Metal Curtain Walls / Water Leakage.
• AAMA 501.3 Field Water Test- Static Method.
• AAMA 502 Field Test - Windows.
• AAMA 503 Field Test - Curtain Walls.


We take a team approach to advising clients on the
right strategies to develop a Sound Envelope and
Sensible Quality Control plans.

866 - 584 - 6868